Grounding
What follows are my thoughts on grounding. There is a lot of misinformation around on
grounding. Some of it is just wrong. Some of it is also dangerous. There are also some grey
areas where we may not know what to do! In that case we try to error on the side of safety.
To fully understand grounding you need to have a knowledge of basic electrical principles.
Without going into detail, you absolutely need to know that current flows from a higher
potential to a lower potential. There must be a complete path for current to flow. This is easy to
visualize with DC and a battery, a little harder with AC and downright difficult with RF.
To make up a simple example, if there are two wires supplying current to your house, one black
and one white, current is considered to flow from the black or hot wire to the white or neutral
wire. There is a “source” where those two wires are connected. Current leaves the source on
the black wire and returns to the source on the white wire. That’s the simple case. In the real
world current leaves the source on the black wire and it’s objective it to find a path back to the
source ( the point where the white wire is connected). In a simple case it’s would be just the
white wire, but in reality it is partly the white wire and also any other conductive path that might
also exist in parallel with the white wire. ( the white wire is connected to the earth ground and
so are a lot of things)
Let’s take a metal light pole as a good example. Two wires can be used to light the light at the
top of the pole. The source is back somewhere up the street in the power system transformer
or substation. It does not matter exactly where, just that there is a source somewhere. The
black wire has 120 volts on it, the neutral is said to be zero. It is in fact connected to the
ground back at the power panel that feeds the light. Now let’s suppose the black wire
accidentally comes in contact with the metal pole. The white wire is not touching the pole.
The metal pole then becomes very dangerous. It has 120 volts on it. Anyone touching the pole
can be killed. Sometimes, in ignorance, the installers of the power pole will drive a ground rod
and connect the pole to the ground rod thinking that makes it safe. All that does is make it
more unsafe! Current will indeed flow from the black wire to ground, but it will only be a few
amps at most. It will not be enough to trip the circuit breaker. So the power stays on. The light
stays on. The pole remains energized with 120 deadly volts. In this case we have current from
the source supplied to the black wire going to the light and returning through the white wire to
the source and we also have additional current supplied going through the pole to the ground.
That current is trying to find find a way to get back to the source. If the pole is only grounded
with the ground rod, the current will flow through the ground back to the source, because in all
cases the source should be grounded. However, the amount of current will not be high
because the return path through the ground rod has significant resistance to limit the current to
only a few amps. What also occurs is a voltage gradient in the vicinity of the pole where
dangerous voltages occur. The voltage at the copper ground rod will be 120 volts. Just a few
inches away from the ground rod, the voltage might still be 100 volts. As you move farther from
the ground rod the voltage decreases until at somewhere from 25 to 50 feet it becomes zero.
We call that the zero ground potential. Remote earth ground is always at zero volts. So the
voltage from remote earth to the light pole is 120 volts. The voltage from the ground right at the
pole to the pole is more like 100 or 110 volts. There have been many cases of people being
killed by touching a metal pole that has been energized like this. The existence of a ground rod,
grounding the metal pole, does nothing to make that pole safe. What does make it safe is to
have that third conductor which is called a safety ground connected to the metal pole and
running all the way back to the power panel. With that ground, the breaker will trip if and when
the black wire inadvertently makes contact with the metal pole. Never cut off or defeat the
grounding prong on an ac electrical cord or you will create this dangerous situation on
whatever equipment that power cord supplies.
If a person were to touch such a power pole with a fault as I have described, their body would
provide a parallel path for the current to travel to ground. The current would then divide up
between the ground connection and the body path. How much current goes which way would
depend on the resistance of each path. It does not take much current to kill. Even though the
ground is considered to be a conductor, making a good contact with the ground is very
difficult. A ground rod does not make very good contact. The path back to the source through
the ground rod to earth path is nowhere near as good as that single wire used as a safety
ground.
The National Electric code only requires the ground rod to have a resistance around 25 ohms.
The fault current in that case (black wire connected directly to the ground rod) would be 120/25
or 4.8 amps. That would not be enough to trip the circuit breaker. In most cases a single
ground rod will not be that good.
This concept of a potential gradient in the vicinity of a ground rod is significant not only in a
case like this where 120 volts is inadvertently connected to it but also in a great many other
cases such as a lightning strike. More about that as I get into details about grounding in a ham
radio station.
The circuit or that part of a circuit that is made up by the copper ground rod, it’s contact
resistance with the earth touching the bare copper and the actual dirt, concrete, and other
materials that make up the ground in the vicinity of the ground rod out to some distance of 25
or more feet to the point that can be called remote earth ( where the normal potential is that
theoretical zero potential) has a resistance. That resistance is never zero, but can be made
fairly low. It can be thought of as several series resistors. For example, in the case of a single
long copper ground rod, that resistance might total 25 to 50 ohms. In a simplistic case, as a
start in understanding it, it could be thought of as a 20 ohm resistance ( the contact resistance
of the rod to the dirt it actually touches) in series with maybe a 10 ohm resistor representing the
next foot or so of dirt, then in series with maybe a 5 ohm resistor representing the next 10 feet
of dirt and finally a 2.5 ohm resistor representing the rest of the distance out 50 or so feet to
remote earth. Add those up and the resistance to our estimated zero potential earth point is 20
+ 10 + 5 = 35 ohms. The reason I have used decreasing resistors as we moved away from the
ground rod is that as we spread out from the rod we will have more and more parallel paths for
the current to take. Any time you provide a parallel path, you decrease the resistance. For
instance if one chunk of earth has 10 ohms of resistance and you add another chunk
alongside it where the current can also flow, you cut the resistance down to 5 ohms. As the
current travels away from the ground rod there is more and more dirt available creating less
and less resistance. Consequently the voltage gradient that exists around and out from the
ground rod is not a set number of volts per foot. To keep it simple, the resistance decreases
each foot you move away from the ground rod, therefore the voltage drop or change in
potential is less and less per foot as you move away from the rod. The first 6 inches is a high
resistance and a large voltage drop can exist very close to the rod. The voltage drop across
each foot of earth becomes less and less as you move away. You can look at this several ways.
First of all, what is significant is the difference in potential or voltage between two points. If you
get across two points with a high enough potential you can be shocked or killed. If the ground
rod is energized with 120 volts and you touch it with your feet on the ground you will get a
shock. If you are insulated from the ground you may not feel a shock. To take the unknown
shoe resistance out of the equation, let’s say you are barefooted. Standing with your feet 50
feet from the ground rod and if you could touch the rod with a long stiff copper wire, you would
get shocked with the full 120 volts. Move in to about 5 feet from the rod and you would be
shocked with about 100 volts. Move even closer to 1 foot away. At one foot you would be
shocked with only 82 volts! Still enough to be lethal! Move in to within 6 inches. At that point
you would be shocked with 62 volts. What you are feeling is the difference in potential caused
by the voltage difference created by the current flow through the resistance of the ground to
the point where your feet are touching the ground.
Suppose you do not touch the ground rod. Let’s say you are standing on the ground five feet
away and bend over and touch the ground that is 3 feet away from the rod. The potential
difference of those two points is what could shock or kill you! It is quite possible that that
voltage would be 15 volts more or less. You would feel that. How bad the shock would be
depends on moisture on you skin, the ground composition and other vague factors. However, if
the voltage on the ground rod was 1200 volts instead of 120 volts, you would be killed, as the
potential difference between those two points would be 150 volts instead of only 15.
This is why you never want to get close to a live power line that touches the ground or even
concrete. It causes a voltage gradient in the nearby earth.
You can illustrate this by placing a dot in the center of a piece of paper to represent the ground
rod and drawing 10 concentric circles around the dot. The outer most circle represents the zero
potential point and the dot can represent 120 volts. The first circle would be 90 volts, the
second circle would be 100 volts, the fourth circle 110 volts, the eighth circle 115 volts and the
last circle 120 volts. These numbers represent the voltage measured from that point on the
ground to the rod. It is called the touch voltage. The voltage you would feel if you touch the
ground rod when it is energized with 120 volts.
If you want to see the absolute earth potential, you can label the first circle 110 volts, the
second circle 100 volts, the forth circle 90 volts volts, the eights circle 10 volts and the outer
circle zero volts to represent the absolute remote earth potential of zero. This is a better way of
looking at it from an engineering point of view, but the touch voltage may be better from a
practical understanding as it indicated what voltage you could actually feel.
If the wire contacting the ground is a 7200 volt power line, then the ground potential five feet
away is probably 6000 volts and very high voltages extend out considerably farther! There is a
term called step potential. It is the voltage difference between your feet. If that voltage
difference is high enough it could be very dangerous. For example, in a car accident involving a
downed high voltage power line, you should stay in your car. Just walking on the concrete or
earth near a high voltage wire could likely kill you. If you must get out of your car, the
recommendation is to jump out with both feet together. Then continue jumping with both feet
together away from the wire. It is possible that there could be extremely high voltage points
existing just in the distance of one step. By keeping both feet together you are trying to be like
that bird on a high voltage wire that does not get shocked! Even though the voltage on the
earth may be several thousand volts, if you keep both feet together, you can minimize the
voltage difference. Only do this if you must leave your car due to fire or smelling gas and fear of
an explosion.
We can now bring into this discussion a lightning stroke. When the lightning hits the ground,
either directly or through a tree or tower, it causes a potential gradient to exist out significant
distances from the strike. It also sends out a short duration pulse of electromagnetic wave.
If you have two ground rods, say 50 feet or so apart, the ground potential at those two points
could be a thousand volts or more apart. This will cause significant current to want to flow from
one rod to the other. If it has no other choice it will flow through the ground. However if there is
a better path, some or maybe most of the current will take it. That path could be through
equipment that is connected to both ground rods. The ground rod at the power panel is the
primary ground rod. The one that hams put at the radio is a secondary or auxiliary ground rod.
In order to minimize (Note I did not say prevent) damage, the auxiliary ground rod must (by the
electrical code) be bonded or connected to the primary ground rod with at least a number 6
copper wire (or equivalent capacity aluminum wire).
In addition to the potential problems caused by lightning hitting the ground, the strike will
create an electromagnetic pulse. It is a short duration pulse. Such a short pulse will contain
high frequency components and may be at the equivalent frequency of one megahertz. It will
induce currents into nearby conductors. Since it is what I will call a high frequency pulse, the
voltages created by the current are not simply current times the resistance of the wire, but
current times the impedance. This impedance includes reactance. Inductive reactance of a wire
may be minimal under normal ac or dc situations, but can be significant where lightning pulses
are concerned. We need to be concerned with voltages on wires ( whatever they are normally
carrying is not important here) rising high enough in potential with respect to anything they are
in close proximity to where there will be damage caused by this over voltage situation. If the
radio chassis is connected to a ground rod that rises several thousand volts above the power
wires from a panel grounded to a different rod, we most likely will have damage. If the ground
rod rises in potential, thus elevating all the power from it to your radio, but the radio chassis is
held at a lower potential by its ground rod, we again could have a problem. Bonding the two
ground rods with as short and straight a No. 6 wire as possible will help somewhat.
Why is a number 6 wire required? The answer is that the lighting pulse is a short duration,
equivalent to about a 1 MHz frequency and the surface area is more significant than the cross
sectional area of the wire. The NEC has deemed a No. 6 copper wire is what is required.
Next there are three reasons to ground.
The first two concern the power system ground.
First of all, there is the safety reason. This applies when we are connected to 120 or 240 volt
ac. The commercial power at your house or building will have a single point ground. For 120
volt ac there will be a black wire, a white wire and a bare (or green wire). The black wire is
referred to as the “hot” wire. The voltage (or potential) between the black and white wire will be
120 volts. The white wire will be at about the same potential as ground. It will be connected to
the ground rod through the power panel. This used to be all there was in a home. As long as
you connected your lamp, tv, radio, power saw or whatever to the black and white wire you
had power and your device worked. This was not very safe. Sometimes you could plug in your
radio set the wrong way and the hot wire would be connected to the metal case and you could
get a nasty shock. At some point they started using polarized plugs so you could not plug
things in the wrong way. This helped. Eventually we got to where we are now. We normally
have plugs with three prongs. One to the black (hot) wire, one to the white wire and one to a
third wire, which is usually bare or green. If your device has a metal case or metal chassis, the
third wire is connected to it. The black wire and the white wire are intended to carry the current
to operate your device. The black wire is referred to as the hot wire or hot conductor. The white
wire is the grounded conductor. It is a conductor like the black wire but it is also connected to
the ground rod back at the power panel. The “third” wire is called the grounding wire. It is not
supposed to carry current. If there is some problem where the black wire comes in contact with
the case of the device current can flow through this third wire back to the power panel and trip
the circuit breaker. This third wire is usually smaller than the conductors carrying current to run
your device, because it only has to carry short circuit current for however long it takes to trip
the breaker. Small wires can carry 15 or 20 amps for short periods of time while they would
overheat if they had to carry that current for a long period of time.
So for safety we have a ground at the power panel and two of our wires from every outlet run
all the way back to the power panel where they all connect together at one place where there is
another wire that runs to the power ground rod. This is all for safety. Mostly personal safety.
The second reason for the power ground is to protect the equipment from lightning surges.
Note I did not say protect anything from a direct hit by lightning, I said protect equipment from
damage by a lightning surge. That is protection from a nearby lightning strike.
Strange things happen when lightning is nearby. We think of ground as at zero volts. We think
of the white wire as at ground potential and the black wire as -/+ 120 volts from the white wire
and the same from the grounding wire. However, in an ungrounded system during a nearby
lightning strike, the voltage induced on the power wires can rise to extremely high values. For
example, inside a machine that is bolted to the concrete floor, the voltages on the power wires
can get so high that current may arc through the 600 volt insulation to the machine case or
foundation or whatever happens to be connected to the foundation. Major damage can occur
to the equipment. It is possible for anyone nearby to be also hurt or killed due to this lightning
surge. The solution was to use a grounded power system so that when the voltage on the
power wires increased due to the surge, everything in the area also increased in potential. In
that case there would be no large potential developed between the power wires and the
equipment case or foundation.
Originally electrical systems were ungrounded, but these types of problem caused a change to
be made to grounded systems. It can be confusing at first.
Even though we think of the ground, everywhere, being at the same potential, there are some
subtle issues. First of all, even though the resistance of the ground from one place to another
may be really low, connecting to the ground is not easy. When a ground rod is driven into the
ground, there will be a contact resistance. Let’s suppose we go to one of our receptacles in our
house, that is not protected by a ground fault breaker and do a simple test.
We take a long black wire and connect to a standard 120 volt plug on the hot side. Then we
run that black wire out to the middle of our back yard and connect it directly to a ground rod.
What will happen when we plug it in to the receptacle? Most people think it will trip the 15 or
20 amp breaker. Let’s think about what we have. We do have a complete circuit. There is a
path for current to flow from the breaker through the black wire to the ground rod, into the
ground, through the ground and to the power system ground and ultimately back to the source.
If we take our volt meter, and measure voltages we will read 120 volts ac from the breaker to
the ground bus in the panel where all the white wires are connected. We will read 120 volts
from the ground rod in the middle of our back yard to the ground bus in the power panel. No
surprise in those measurements. If we measure from the power system ground rod to out
ground rod where we connected our black wire we will also get 120 volts ac. This voltage is
pushing a current through the ground. If the ground had no resistance we would trip the
breaker. Current equals 120 volts divided by the resistance. If the resistance was 6 ohms we
would have 120/6 equals 20 amps. That would trip our 15 amp breaker. However most of our
resistance will be at the point where the ground rod contacts the earth. That contact resistance
will be in series with the actual resistance of the ground or moist dirt. It is quite possible that
we will only have a few amps flowing. There will be what is called a voltage gradient around the
ground rod. Remember we will have a total voltage drop in this (or any circuit) equal to the
source voltage. In our case the source voltage is 120 volts ac. We start at the end of our black
wire with 120 volts with respect to the white wire or white wire bus. As we move away from the
ground rod, that voltage will decrease until it reaches zero (the same as the white wire or white
wire bus. This change in voltage as we move away from the ground rod is not linear. It changes
rapidly in the first few feet then the change in voltage per feet will be less and less.
The voltage at the ground rod will be 120, about a foot away it will be around 80 volts, 3 feet
away it will be 90, 5 feet away it will be maybe 103, at 25 feet away it will be 120. So it will take
about 25 feet to zero volts or in other words get back to ground potential, which is zero volts.
There are well established power tables that give this information.
Another example is metal power poles. With the old two wire systems, if a pole was energized
with 120 volts by a fault or any other reason, you could get shocked touching it. The first
answer was to drive a ground rod and ground it. Problem solved. NO! With a contact
resistance of 25 ohms the ground rod did not protect anything. The solution was to run a
grounding conductor back to the same place as the white wire! Standing at the pole with only a
ground rod could still pose a severe electrical shock or death.
Note the utility has multiple grounds on their side ( service side) of the home panel box. It’s ok
for them to do it but it’s not ok on the load side of the panel box.
We think of the neutral or white wire as being zero volts because it’s grounded, but that’s not
really true. While the neutral (white wire) might be zero at the transformer, the neutral wire
carries load current and has resistance. Therefore because it carries current and has
resistance, there will be a voltage drop. Current times resistance or IR drop.
In reality there will be a voltage on the neutral wire. It should be small, but it can be measured.
It will vary depending on the load on the utility. It is called the NEV or Neutral to Earth Voltage.
The neutral wire will carry load current back to the substation transformer. There is a resistance
in that wire, however there are parallel paths through the ground where current will also flow
back to the substation. In fact there are many many parallel paths and they all reduce the
current flowing in the neutral conductor and therefore that reduces the IR drop in the neutral
conductor.
Let’s think about the concept of neutral earth or remote neutral earth. That is a place where no
current is flowing and therefore the potential can really be zero. For all practical purposes that
is probably 50 feet or so from any ground rod that is connected to a neutral. You can go and
stick a meter lead in the ground at that point and then connect the other lead to your panel box
and read a small voltage. Could be .5 volts or it could be 2 volts. It is simply the result of
neutral current flowing in the utility system multiplied by the resistance of the neutral path. It
typically increases the farther you are from the substation. It will also be constantly changing as
the load on the utility system changes.
One important note here. If the potential between the black and white wire is 120 volts and the
voltage from the white wire to ground is zero, then the voltage from the black wire to ground is
120. However, if the system neutral is at 2 volts, then the voltage from the black wire to ground
becomes 120 plus 2 or 122. This might not seem significant at this point, but if for some
reason, like a nearby lightning strike some ways from away, voltages are induced in the power
cables they we could have several thousand volts on the black and white wires above ground,
while still having 120 volts between them. If we have a dedicated ground on our equipment
(radio) then the chassis of the equipment will be held to the potential of the local ground. Let’s
call that zero or near zero volts. In that case we can have equipment failure because it can not
handle the power wires inside the equipment being several thousand volts higher than the
chassis. We need the chassis of the equipment to “ rise up” so, for example, the insulation in
the power transformer does not arc to the chassis, thus at a minimum blowing the transformer.
In a similar manner, a nearby lightning strike could cause the local ground to raise up much
higher than the ground back at the substation. In that case the chassis ground could rise up
while the power lines are still 120 volts above the utility ground but become significantly
different than the dedicated equipment ground causing similar equipment damage.
You never ground a piece of equipment to a ground that is different ( not bonded to) the system
ground at the power panel.
The third reason is the ham radio or antenna reason. This gets even more vague and
complicated than the electrical safety and lightning reasons.
First of all a ham radio does not need a ground to work. There are cases where a ground may
compensate for some other problem and appear necessary. There are cases where the ground
is actually used as half of the antenna. I will try and address all these cases.
The transmitter is a source of power similar to the utility power generators. At the output
connector of the transmitter there is a push and a pull of current. However much current leaves
the transmitter at any given instant an equal amount of current must return. With a balanced
dipole it is easy to see. We can visualize current going out to one side of the dipole escaping
into the air and returning back on the other side of the dipole and down the transmission line to
the transmitter ( source) .
No ground is involved is this situation. Ground does get involved in reflecting the radiated
wave, but that’s another issue.
In most antennas, we can easily understand where the current that is leaving the transmitter
goes. It goes out on one wire of the transmission line and out on the antenna to (hopefully) be
radiated. In all cases, an equal amount of current must return to the transmitter (source). I can
state that another way, however much current returns to the transmitter will be exactly equal to
the amount of current that left the transmitter. If no current returns then no current can leave.
It’s just that simple.
Let’s take the extreme case of a simple end fed wire. It can be a half wave or any length.
We visualize current going up the coax center conductor and out on the wire. Where is the
return current. We need to see the complete circuit. In the dipole it came back to the opposite
half of the antenna. In this end fed example we do not see that half. In all cases that current is
looking for a path back to the transmitter ( source). If it only finds a high impedance or high
resistance path that will limit the current that can even go out on the antenna in the first place.
One path that will exist is the outside of the coax feed-line. In this case the outside of the feed-
line acts like the other half of a dipole. Current will flow on the outside of the coax and back to
the transmitter (source). Current may enter the ground and return through the ground rod and
up the ground wire that was installed at the station for whatever reason. Maybe it was installed
for this very reason. Another way for current to return to the source is by entering a ground
radial system or a set of counterpoises that were designed to capture these return currents.
However it is done, some means must exist for return current to get back to the source.
I think it’s a mistake to think of a ground as some sort of attraction for radio frequency energy
that will send unwanted signals to ground. Remember that current only wants to get back to
the source. That “source” will be a potential difference. If a potential difference (voltage) exists,
it wants to push the current from the high potential to the low potential. Looking at the output
of a transmitter as a source having two terminals, one terminal wants to push current out and
the other wants to pull it in. The ground is not necessary.
A power substation wants to push current out (eventually to the black wire in your house) and
suck it back from wherever it can. The transmission line for the dipole wants to push it out on
one wire and suck it back on the other. The transmission line for the end fed antenna wants to
push it out on the wire and suck it back from wherever it can.
Charged clouds in the atmosphere build up larger and larger charges until the air can no longer
act as an insulator and the clouds discharge through the air to the earth or something
connected to the earth. I really don’t know or care which direction it goes. Electrons go one
way, positive ions go the other way and current is defined to be in the direction that a positive
test charge will move when placed in an electric field. It really doesn’t matter.
We do know that lightning is an electrical arc of high current for a short duration.
The best we can do is to bleed off excessive charge ( static electricity or induced electricity)
with some sort of “spark plug” device on our feed-lines. That stops the buildup of excessive
voltage between the two conductors of whatever kind of feed-line we use.
We also should have a device to bleed off charge in the feed-line to ground. This can also be a
spark plug type of device or a direct ground.
Any direct ground to the radio equipment (if you chose to use one) needs to be bonded to the
power panel ground. In recent years there is a device installed at most building grounds for that
purpose.
Assume lightning could strike the antenna and route feed-lines and take normal precautions
accordingly. Actually lightning could strike anywhere.
In my station, I accept some risk. I physically disconnect antennas and power cords at what I
deem the appropriate times. Always in spring through fall. Usually in winter, but less careful
then. All of my feed-lines run down to the ground before coming to the house. An exception is
that one dipole coax hangs on the house then runs to my antenna switch. I need to have a
better place to support it. That bothers me a bit.
I do not yet have spark plug devices installed nor are my feed-lines grounded before they enter
the house. This is something I might eventually do. At the moment I deemed the risk I am
taking is acceptable to me. I feel simply driving a ground rod outside my radio shack without
bonding back to the power panel is taking unacceptable risk. I do have a ground rod but it is
not connected. I used it for a temporary end fed wire test. At some point I should run a wire
from it back to the panel and connect the shields of my coax there. That is low on my list of
priorities.
I did have a 160 meter dipole struck by lightning twenty years ago. The wire was destroyed.
The coax also severely damaged and had to be replaced. My main radio was disconnected. No
damage. One radio had its power supply plugged in to a wall outlet. It was blown out of the
wall outlet. The plug was an old black plug with a fuse in each side. It was shattered into many
pieces. Ten years later I found part of the plug on the opposite side of the room. No damage to
the power supply other than needing a new plug and fuses! It still works as of December 2021.
The ethernet modem in my computer had the top blown off of several integrated circuit chips. I
simply replaced the modem card and the computer still worked. A laptop computer was
plugged in and I had to replace the power supply. Computer still worked. Two TV sets were
affected by the pulse and simply had to be degaussed. They were probably within 50 feet of
the strike or strikes. I feel that what I did then and what I am doing now is sufficient for me. I
have been close to enough lightning strikes to have a healthy respect for its power. I think it
can strike most of my antennas and although the antenna may not survive, I expect my
equipment to survive. That is unless I forget to disconnect it.
I have all my equipment chassis connected together (K3, Drake L7 amplifier and Ranger II ).
Normally the Drake L7 is unplugged from the wall. With the bonding wire all the chassis on my
desk are at the same potential for safety and tied to the main power panel through the third
wire ground.
Everything is also connected by virtue of the coax shields. The one feed-line that enters the
shack is disconnected for lightning.
The two receive antennas are BOGs (wires running on the ground). There is no ground
associated with the feed-lines at all. Each end of the receiving wire is grounded, however it is
isolated from the feed-line by a transformer. A nearby lightning strike could fry the terminating
resistor and the transformer. Since the feed-lines are either on the ground or in the ground, I
feel fairly safe. I suppose I could do more, but in 60 years of having antennas I don’t see the
value of doing more, yet. Of course these antennas are also normally disconnected from the
receiver.
Antennas
A dipole antenna does not require a connection to ground in order to function as an effective
radiator. Neither does any Yagi or other balanced antenna. They are what I call complete or self
contained antennas.
There are come “incomplete” antennas that need either a counterpoise, ground plane or some
sort of image antenna to complete the antenna or antenna circuit. Without the intentional
addition of such circuit, the RF energy pushed out on the antenna will attempt to find its own
way back to the source and whatever conductive or semi conductive path it takes will, in
effect, become a part of the antenna. I suggest that in most cases this will not be the best
situation. Seemingly unrelated changes can then have significant effects on antenna
performance. The same antenna, moved or installed elsewhere may have totally different
performance. In some cases a ground is used in order for the antenna to work reasonably well.
In these cases, the length of the ground wire is significant and frequency sensitive. The ground
wire is also a radiating part of the antenna. The coax shield, if such an antenna is fed with
coax, will also become a radiating part of the antenna.
Even with so called balanced antennas as well as antennas that use a ground system to
complete the antenna circuit, the coax could inadvertently become a part of the radiating
antenna system. It all depends on the impedances of the ground system, impedance looking
down the outside coax shield, and the physical orientation of the coax feed-line in the antennas
radiation field. Again the length of the ground wire as well as the length of the coax feed-line
and any other conductors that may be connected affect how much current flows and where it
flows.
It is always best to install a complete antenna and attempt to not have any radiating portions
running to the operating position. Not only is safety from shock important but radiation safety
becomes a consideration with power over a certain threshold depending on frequency. When I
used end fed antennas, I limited my high power operations to only the lower bands. I still have
one end fed antenna. Is is really a ground mounted top loaded vertical commonly called an
Inverted L for 160 meters. The coax runs out, partly underground and along the ground, to the
base of the antenna where I have a ground rod and one or more radials. The antenna wire is
series fed through a capacitor, so if the voltage on the wire built up high enough it could arc
across the capacitor and from the center conductor to the shield of the coax to get to ground. I
think a direct lightning strike would find its way to ground at the ground rod near the base of
the antenna. I accept the chances that the coax would be destroyed along with the antenna
wire and the capacitor. A spark gap should be installed to discharge the wire to the ground rod.
With balanced antennas, you are concerned with keeping common mode currents off the
outside of the shield. You look at the shield as two conductors. The inside of the shield and the
center conductor being the two conductor feed line and the outside of the shield being the
third conductor. Current on the inside of the shield would be equal to the sum of the current on
the side of the antenna connected to the shield plus the current flowing on the outside of the
shield. To avoid current flow on the outside of the shield there are several things that can be
done if necessary. Basically, you want the impedance that the current “sees” looking back
down the outside of the shield to be several times greater than the impedance looking out on
the antenna wire.
The impedance of the half antenna is pretty much fixed, but the impedance looking down the
third wire ( outside shield of the coax) varies with the length and location of the shield and
whether or not it is grounded at the radio and/ or connected to any other conductors. It can be
next to impossible to predict exactly what this impedance will be. If this third wire is open
ended and a quarter wave long, it will have a high impedance at the end, but back at the
antenna feed point it will have an impedance close to the actual antenna wire impedance, so
theoretically it will carry half the antenna current. In other words the current will see equal
impedances and will split 50/50. I think this is the worst case. If the coax, in this ungrounded
situation, is longer or shorter than one quarter wave then the impedance looking down the
outside of the coax will be greater than the antenna wire and the current will divide accordingly
and more will end up on the antenna.
A choke can be put in the coax near the feed point to insure a high impedance in this third wire
path. That is the only thing I do, if I do anything. Another popular solution is to use a current
balun. Pretty much that is the same thing as a choke. They can be made one of several ways.
One need to be careful that impedances are correct and the voltage, current and power ratings
are not exceeded. What is designed to work under a given set of conditions, may not work if
not used under those same conditions. I have known people to burn up balun so with far less
power than it’s rating.
It is frequently unnecessary to do anything other than connect the coax and see how the
antenna performs. Some radiation from the feed line is not always a problem, however with a
directional antenna, such as a Yagi, it may degrade the directive pattern. With dipoles
directivity is not much of a concern.This may or may not be acceptable in a particular specific
case.
The simplest and probably the most reliable method is to use the feed-line itself to make the
choke. That way there are no connections to make or go bad. This type of choke is simply
several turns of the coax feed-line taped together. The diameter and number of the turns can
be tailored to suit the frequency range of the antenna. This is my preferred method if I choose
to do anything besides feeding the antenna directly with coax.
Notes:
A ground is not necessary for a ham radio station in many cases.
Radio equipment should be connected back to the building electrical panel ground bus
through the “third wire” or ground wire in the power system. This is for safety.
Coax cables should have devices to bleed off charge from the center conductor to ground.
(Poly phasers or “blitz-bug” type of spark gap.
The shield of the coax may be connected to ground outside the radio station. This ground
should be bonded with a number 6 (minimum) copper wire to the building IBT or intersystem
bonding termination.
In most cases the ground is for safety or to provide a path for a lightning surge but not for a
direct lightning strike.
Connecting a piece of equipment to a isolated or stand alone ground rod does not make it any
safer to touch, but most people think it does!
In some cases a ground connection is used to compensate for using half of an antenna, or to
attempt to compensate for a poor design or poor installation.
Currents always return to the source and an antenna circuit is no different. Current leaving one
antenna terminal must complete the circuit by flowing back to the other or opposite terminal.
Antenna currents may return through the ground on their way to that terminal. If that terminal is
connected to only a ground rod, then it will become the return or part of the return. It depends
on the antenna and what other conductors are nearby and may be intentionally or inadvertently
connected or coupled to the equipment / antenna. Although the ground may be a good
conductor, the ground rod only makes contact over a small contact area and that is not good.
For this reason, multiple ground rods and radial systems are frequently used with bottom fed
verticals or monopoles. Typically these verticals are only half of the antenna. They are not what
I would call “self contained” verticals. A vertical center fed dipole would be a “self contained”
vertical. A half square would also be a SCV or self contained vertical. They do not need a
connection to ground or any kind of radial system.
It is important to recognize the different functions that the earth plays under a ground mounted
vertical and several wavelengths out in front of the vertical. The close in earth or ground system
can minimize or cause loss. The far earth or ground (we have no control over that other than
choosing to install the vertical antenna on the ocean shore) has to do with how good the
reflections are and how much gain there is at the receiving station. It does not affect the shape
of the pattern, just how large it is. With horizontal antennas the quality of the near and far earth
( ground) is not very important. Vertically polarized waves are affected quite differently than
horizontally polarized waves when reflected from earth (ground).
Comments
Post a Comment